Haifeng Machinery

Baudouin 6M11G150/5 vs Cummins QSB5G6

Compare Baudouin 6M11G150/5 and Cummins QSB5G6 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 6.6 L and 4.5 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.

SpecificationBaudouin 6M11G150/5Cummins QSB5G6
Standby electrical (50 Hz)120 kWe120 kWe
Prime electrical (50 Hz)108 kWe109 kWe
Standby electrical (60 Hz)132 kWe125 kWe
Prime electrical (60 Hz)120 kWe113 kWe
Other recorded mechanical power (duty unspecified)Not listed155 kW
Displacement6.6 L4.5 L
ConfigurationL6L4
Cylinders64
Recorded engine speed1,500 RPMNot listed
FuelDieselDiesel
CoolingLiquid-CooledLiquid-Cooled
Recorded emissions classificationUnregulatedU.S. EPA Tier 3 / EU Stage IIIA / China III
Dry weightNot listedNot listed
OriginFranceUnited States / United Kingdom

Compare matching ratings

Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.

An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.

Baudouin 6M11G150/5: Review the model record and available supporting documents

Cummins QSB5G6: Review the model record and available supporting documents

Choosing between Baudouin 6M11G150/5 and Cummins QSB5G6

Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.

With your permission, we use analytics to improve engine search and understand which pages lead to enquiries. The catalog works without analytics.

Essential storage — always on

Remembers your choice for 180 days in this browser on this site.

Google Analytics and Vercel Analytics measure page views, search results and enquiry-link clicks. Our custom events exclude raw search text. A link click is not a submitted enquiry.

Change your choice in the footer at any time. Turning analytics off reloads the page.