Baudouin 6M16G2D0/S vs Perkins 1206J-E70TTAG3
Compare Baudouin 6M16G2D0/S and Perkins 1206J-E70TTAG3 by recorded output, operating duty, frequency and engine specifications. Their listed displacements are 9.726 L and 7.01 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Baudouin 6M16G2D0/S | Perkins 1206J-E70TTAG3 |
|---|---|---|
| Standby electrical (50 Hz) | 176 kWe | 175 kWe |
| Prime electrical (50 Hz) | 160 kWe | 159 kWe |
| Standby electrical (60 Hz) | 200 kWe | 149 kWe |
| Prime electrical (60 Hz) | 180 kWe | 135 kWe |
| Other recorded mechanical power (duty unspecified) | 238 kW | 184 kW |
| Displacement | 9.726 L | 7.01 L |
| Configuration | L6 | L6 |
| Cylinders | 6 | 6 |
| Recorded engine speed | Not listed | 1,500 RPM |
| Fuel | Diesel | Diesel |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | Unregulated | Euro Stage V / U.S. EPA Final Tier 4 |
| Dry weight | Not listed | Not listed |
| Origin | China | United Kingdom |
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Baudouin 6M16G2D0/S: Review the model record and available supporting documents
Perkins 1206J-E70TTAG3: Review the model record and available supporting documents
Choosing between Baudouin 6M16G2D0/S and Perkins 1206J-E70TTAG3
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.
