Baudouin 6M16G4N0/5 vs Generac SG150 (9.0L)
Compare Baudouin 6M16G4N0/5 and Generac SG150 (9.0L) by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 9.6 L and 8.9 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Baudouin 6M16G4N0/5 | Generac SG150 (9.0L) |
|---|---|---|
| Standby electrical (50 Hz) | Not listed | Not listed |
| Prime electrical (50 Hz) | 150 kWe | Not listed |
| Standby electrical (60 Hz) | Not listed | 150 kWe |
| Prime electrical (60 Hz) | 180 kWe | Not listed |
| Other recorded mechanical power (duty unspecified) | Not listed | 171 kW |
| Displacement | 9.6 L | 8.9 L |
| Configuration | L6 | V8 |
| Cylinders | 6 | 8 |
| Recorded engine speed | 1,500 RPM | 1,800 RPM |
| Fuel | Natural Gas | Natural Gas |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | Unregulated | U.S. EPA Stationary |
| Dry weight | Not listed | Not listed |
| Origin | France | United States |
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Baudouin 6M16G4N0/5: Review the model record and available supporting documents
Generac SG150 (9.0L): Review the model record and available supporting documents
Choosing between Baudouin 6M16G4N0/5 and Generac SG150 (9.0L)
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.