Cummins B6.7G17 vs John Deere 6068HFG20
Compare Cummins B6.7G17 and John Deere 6068HFG20 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 6.7 L and 6.8 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Cummins B6.7G17 | John Deere 6068HFG20 |
|---|---|---|
| Standby electrical (50 Hz) | 137 kWe | 137 kWe |
| Prime electrical (50 Hz) | 124 kWe | 125 kWe |
| Standby electrical (60 Hz) | 155 kWe | 143 kWe |
| Prime electrical (60 Hz) | 141 kWe | 130 kWe |
| Other recorded mechanical power (duty unspecified) | 183 kW | Not listed |
| Displacement | 6.7 L | 6.8 L |
| Configuration | L6 | L6 |
| Cylinders | 6 | 6 |
| Recorded engine speed | Not listed | 1,500 RPM |
| Fuel | Diesel | Diesel |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | U.S. EPA Final Tier 4 / EU Stage V | Unregulated |
| Dry weight | Not listed | Not listed |
| Origin | United States / United Kingdom | United States |
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Cummins B6.7G17: Review the model record and available supporting documents
John Deere 6068HFG20: Review the model record and available supporting documents
Choosing between Cummins B6.7G17 and John Deere 6068HFG20
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.