Mitsubishi S12A2-PTA vs VMAN D22.2
Compare Mitsubishi S12A2-PTA and VMAN D22.2 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 33.93 L and 21.927 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Mitsubishi S12A2-PTA | VMAN D22.2 |
|---|---|---|
| Standby electrical (50 Hz) | 708.8 kWe | Not listed |
| Prime electrical (50 Hz) | 644.8 kWe | Not listed |
| Standby electrical (60 Hz) | 807.2 kWe | 711 kWe |
| Prime electrical (60 Hz) | 723.2 kWe | 646 kWe |
| Displacement | 33.93 L | 21.927 L |
| Configuration | V12 | V12 |
| Cylinders | 12 | 12 |
| Recorded engine speed | 1,500 RPM | 1,800 RPM |
| Fuel | Diesel | Diesel |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | Unregulated | Unregulated |
| Dry weight | 3,400 kg | Not listed |
| Origin | Japan | China |
Mitsubishi S12A2-PTA: Electrical output includes catalog estimates. Check the calculation basis and source document on the model page; these are not verified complete-generator ratings. Rating details
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Mitsubishi S12A2-PTA: Review the model record and available supporting documents
VMAN D22.2: Review the model record and available supporting documents
Choosing between Mitsubishi S12A2-PTA and VMAN D22.2
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.