SDEC 6KTAA25-G35 vs Weichai 6M33D572E200

Compare SDEC 6KTAA25-G35 and Weichai 6M33D572E200 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 25 L and 19.8 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.

SpecificationSDEC 6KTAA25-G35Weichai 6M33D572E200
Standby electrical (50 Hz)515 kWe515 kWe
Prime electrical (50 Hz)468 kWe468 kWe
Standby electrical (60 Hz)Not listed570 kWe
Prime electrical (60 Hz)Not listed518 kWe
Other recorded mechanical power (duty unspecified)Not listed633.3 kW
Displacement25 L19.8 L
ConfigurationL6V6
Cylinders66
Recorded engine speed1,500 RPM1,500 RPM
FuelDieselDiesel
CoolingLiquid-CooledLiquid-Cooled
Recorded emissions classificationChina National Stage III / UnregulatedChina National Stage II / Unregulated
Dry weightNot listed2,090 kg
OriginChinaChina

Compare matching ratings

Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.

An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.

SDEC 6KTAA25-G35: Review the model record and available supporting documents

Weichai 6M33D572E200: Review the model record and available supporting documents

Choosing between SDEC 6KTAA25-G35 and Weichai 6M33D572E200

Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.

With your permission, we use analytics to improve engine search and understand which pages lead to enquiries. The catalog works without analytics.

Essential storage — always on

Remembers your choice for 180 days in this browser on this site.

Google Analytics and Vercel Analytics measure page views, search results and enquiry-link clicks. Our custom events exclude raw search text. A link click is not a submitted enquiry.

Change your choice in the footer at any time. Turning analytics off reloads the page.