Cummins L9G18 vs FPT C90 TE2
Compare Cummins L9G18 and FPT C90 TE2 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 8.8 L and 10.3 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Cummins L9G18 | FPT C90 TE2 |
|---|---|---|
| Standby electrical (50 Hz) | 249 kWe | 250 kWe |
| Prime electrical (50 Hz) | 228 kWe | 225 kWe |
| Standby electrical (60 Hz) | 258 kWe | 300 kWe |
| Prime electrical (60 Hz) | 235 kWe | 270 kWe |
| Other recorded mechanical power (duty unspecified) | 302 kW | Not listed |
| Displacement | 8.8 L | 10.3 L |
| Configuration | L6 | L6 |
| Cylinders | 6 | 6 |
| Recorded engine speed | Not listed | 1,800 RPM |
| Fuel | Diesel | Diesel |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | U.S. EPA Final Tier 4 / EU Stage V | U.S. EPA Tier 3 |
| Dry weight | Not listed | Not listed |
| Origin | United States | Italy |
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Cummins L9G18: Review the model record and available supporting documents
FPT C90 TE2: Review the model record and available supporting documents
Choosing between Cummins L9G18 and FPT C90 TE2
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.