Kohler
Kohler KD36V16
KD Series
Kohler KD36V16 36L 16-cylinder G-Drive diesel engine for generator sets (KD1250–KD1500). 1350 ekW standby at 60Hz / 1500 ekW standby at 50Hz. EPA Tier 2. Turbocharged Aftercooled, Common Rail.
- Standby Power · 50 Hz
- 1,875 kVA
- Electrical Output
- 1,500 kWe
- Cylinders
- V16
- Displacement
- 36 L
- Rated Speed
- 1,500 / 1,800 RPM
Power Ratings
kWm = mechanical shaft power · kWe = electrical output · kVA = kWe ÷ 0.8 pf
50 Hz1500 RPM
| kWm | kWe | kVA | |
|---|---|---|---|
| Prime Power | 1511.1 | 1360 | 1700 |
| Standby Power | 1666.7 | 1500 | 1875 |
60 Hz1800 RPM
| kWm | kWe | kVA | |
|---|---|---|---|
| Prime Power | 1361.1 | 1225 | 1531.3 |
| Standby Power | 1500 | 1350 | 1687.5 |
Kohler KD36V16 generator set context
The Kohler KD36V16 is listed here as a diesel generator-drive engine for 50 Hz and 60 Hz generator sets, with a headline 1,875 kVA / 1,500 kWe / standby rating. Use this page to compare the published engine output, electrical kWe/kVA ratings, emissions level, datasheet availability, and neighboring models before specifying an alternator, controller, enclosure, voltage, and compliance package.
Also searched as
Technical Specifications
| Brand | Kohler |
| Model | KD36V16 |
| Series | KD Series |
| Configuration | V16 |
| Cylinders | 16 |
| Displacement | 36 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | U.S. EPA Tier 2 |
| Country of Origin | France |
Frequently asked questions
What is the power output of the Kohler KD36V16?
The Kohler KD36V16 is rated at 1,875 kVA standby / 1,700 kVA prime at 50 Hz (1,500 rpm); and 1,688 kVA standby / 1,531 kVA prime at 60 Hz (1,800 rpm).
Does the KD36V16 run at 50 Hz or 60 Hz?
The Kohler KD36V16 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Kohler KD36V16 use?
The Kohler KD36V16 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the KD36V16?
The Kohler KD36V16 is a V16 (16-cylinder) engine with a displacement of 36 L.
What emissions standard does the KD36V16 meet?
The Kohler KD36V16 is certified to U.S. EPA Tier 2 emissions standards.
Is the Kohler KD36V16 still in production?
Yes — the Kohler KD36V16 is a current production model.
Is a datasheet available for the KD36V16?
Yes — an official Kohler datasheet for the Kohler KD36V16 can be downloaded from this page.
Related Engines
Compare Kohler KD36V16