Perkins
Perkins 2606AE13TAG4
2606 Series
Perkins 2606AE13TAG4 generator-drive diesel engine discovered in the GenProBase public selector. GenProBase lists 2 row(s) across 50Hz, 60Hz with 12.9 L displacement, 6L cylinders, liquid-cooled cooling, and Unregulated emissions labeling. Treat this row as source-discovered and prioritize OEM datasheet attachment in a follow-up pass.
Chat on WhatsApp about this engine
Opens WhatsApp with Perkins 2606AE13TAG4 and this page link filled in.
- Manufacturer files
- No datasheet
- Last updated
- 2026-08-05
- Package route
- diesel generator sets
- Standby Power · 50 Hz
- 550 kVA
- Electrical Output
- 440 kWe
- Cylinders
- L6
- Displacement
- 12.9 L
- Rated Speed
- 1,500 / 1,800 RPM
Power Ratings
kWm = mechanical shaft power · kWe = electrical output · kVA = kWe ÷ 0.8 pf
50 Hz1500 RPM
| kWm | kWe | kVA | |
|---|---|---|---|
| Prime Power | 435 | 400 | — |
| Standby Power | 478 | 440 | — |
60 Hz1800 RPM
| kWm | kWe | kVA | |
|---|---|---|---|
| Prime Power | 446 | 410 | — |
| Standby Power | 489 | 450 | — |
Perkins 2606AE13TAG4 generator set context
The Perkins 2606AE13TAG4 is listed here as a diesel generator-drive engine for 50 Hz and 60 Hz generator sets, with a headline 550 kVA / 440 kWe / standby rating. Use this page to compare the published engine output, electrical kWe/kVA ratings, emissions level, datasheet availability, and neighboring models before specifying an alternator, controller, enclosure, voltage, and compliance package.
Also searched as
Technical Specifications
| Brand | Perkins |
| Model | 2606AE13TAG4 |
| Series | 2606 Series |
| Configuration | L6, turbocharged aftercooled |
| Cylinders | 6 |
| Displacement | 12.9 L |
| Fuel Type | Diesel |
| Ignition Type | Compression Ignition |
| Cooling Method | Liquid-Cooled |
| Emissions Standard | Unregulated |
| Country of Origin | United States |
Frequently asked questions
What is the power output of the Perkins 2606AE13TAG4?
The Perkins 2606AE13TAG4 is rated at 550 kVA standby / 500 kVA prime at 50 Hz (1,500 rpm); and 563 kVA standby / 513 kVA prime at 60 Hz (1,800 rpm).
Does the 2606AE13TAG4 run at 50 Hz or 60 Hz?
The Perkins 2606AE13TAG4 is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).
What fuel does the Perkins 2606AE13TAG4 use?
The Perkins 2606AE13TAG4 is a diesel generator-set engine.
What is the displacement and cylinder configuration of the 2606AE13TAG4?
The Perkins 2606AE13TAG4 is an inline-6 (6-cylinder) engine with a displacement of 12.9 L.
Is the Perkins 2606AE13TAG4 still in production?
Yes — the Perkins 2606AE13TAG4 is a current production model.