Haifeng Machinery

Cummins QSK38-G11 vs MTU MTU 16V2000 G85

Compare Cummins QSK38-G11 and MTU MTU 16V2000 G85 by recorded output, operating duty, frequency and engine specifications. Their listed displacements are 37.8 L and 31.856 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.

SpecificationCummins QSK38-G11MTU MTU 16V2000 G85
Standby electrical (50 Hz)1,017 kWeNot listed
Prime electrical (50 Hz)920 kWeNot listed
Standby electrical (60 Hz)Not listed1,004 kWe
Prime electrical (60 Hz)Not listedNot listed
Other recorded mechanical power (duty unspecified)Not listed1,115 kW
Displacement37.8 L31.856 L
ConfigurationV12V16
Cylinders1216
Recorded engine speed1,500 RPM1,800 RPM
FuelDieselDiesel
CoolingLiquid-CooledLiquid-Cooled
Recorded emissions classificationChina National Stage III / UnregulatedU.S. EPA Tier 2
Dry weightNot listedNot listed
OriginChinaGermany

Compare matching ratings

Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.

An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.

Cummins QSK38-G11: Review the model record and available supporting documents

MTU MTU 16V2000 G85: Review the model record and available supporting documents

Choosing between Cummins QSK38-G11 and MTU MTU 16V2000 G85

Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.