Liebherr D976 vs Perkins 2806A-E18TTAG4
Compare Liebherr D976 and Perkins 2806A-E18TTAG4 by catalog output, operating duty, frequency and engine specifications. Their listed displacements are 18 L and 18 L, respectively. Start with the same duty and frequency, then check each model’s source and package conditions. These records alone do not establish interchangeability.
| Specification | Liebherr D976 | Perkins 2806A-E18TTAG4 |
|---|---|---|
| Standby electrical (50 Hz) | 624 kWe | 624 kWe |
| Prime electrical (50 Hz) | 556.8 kWe | 565 kWe |
| Standby electrical (60 Hz) | Not listed | 710 kWe |
| Prime electrical (60 Hz) | Not listed | 642 kWe |
| Other recorded mechanical power (duty unspecified) | 850 kW | Not listed |
| Displacement | 18 L | 18 L |
| Configuration | L6 | L6 |
| Cylinders | 6 | 6 |
| Recorded engine speed | 1,800 RPM | 1,500 RPM |
| Fuel | Diesel/HVO | Diesel |
| Cooling | Liquid-Cooled | Liquid-Cooled |
| Recorded emissions classification | Euro Stage V / U.S. EPA Tier 2 | Unregulated |
| Dry weight | Not listed | Not listed |
| Origin | Switzerland | United Kingdom |
Liebherr D976: Electrical output includes catalog estimates. Check the calculation basis and source document on the model page; these are not verified complete-generator ratings. Rating details
Compare matching ratings
Read across a row to compare the same operating duty and frequency. kWe is electrical output; mechanical kW is power at the engine shaft. kVA is apparent electrical power and is shown only when kWe is missing, without converting it. “Not listed” means the record lacks that rating, not zero output. Continuous and prime duties are kept separate. Check source documents, units and site conditions before comparing values.
An emissions classification in the catalog is not proof of certification for your engine or installation. Confirm the exact model, applicable documents and generator configuration.
Liebherr D976: Review the model record and available supporting documents
Perkins 2806A-E18TTAG4: Review the model record and available supporting documents
Choosing between Liebherr D976 and Perkins 2806A-E18TTAG4
Use this comparison as an engineering shortlist, then confirm the complete generator package against load profile, voltage, 50/60 Hz frequency, duty class, emissions rules, cooling margin, altitude, ambient temperature, enclosure design, controller features, and alternator sizing.