Mitsubishi S6R-PTA 24.510L L6 constant-speed diesel engine for generator applications. Official MHI output without fan - 50 Hz: prime 515 kWm at 1500 rpm, standby 570 kWm at 1500 rpm; 60 Hz: prime 595 kWm at 1800 rpm, standby 655 kWm at 1800 rpm. Emissions: Unregulated.

Mitsubishi S6R-PTA 24.51L L6 diesel generator engine — 677 kVA standby specifications
Mitsubishi S6R-PTA 24.51L L6 diesel generator engine — 677 kVA standby specifications
Standby Power · 50 Hz
677 kVA
Electrical Output
542 kWe
Cylinders
L6
Displacement
24.51 L
Rated Speed
1,500 / 1,800 RPM

Power Ratings

kWm = mechanical shaft power · kWe = electrical output · kVA = kWe ÷ 0.8 pf · kWe estimated — see note below

50 Hz1500 RPM

kWmkWekVA
Prime Power515489.6612
Standby Power570541.6677

60 Hz1800 RPM

kWmkWekVA
Prime Power595565.6707
Standby Power655622.4778

Note: The manufacturer does not publish a separate kWe rating for this engine. kWe values shown are estimated from the rated mechanical output (kWm) using a conservative 90% alternator efficiency factor.

Mitsubishi S6R-PTA generator set context

The Mitsubishi S6R-PTA is listed here as a diesel generator-drive engine for 50 Hz and 60 Hz generator sets, with a headline 677 kVA / 542 kWe / standby rating. Use this page to compare the published engine output, electrical kWe/kVA ratings, emissions level, datasheet availability, and neighboring models before specifying an alternator, controller, enclosure, voltage, and compliance package.

Also searched as

s6rptaS6R PTAMitsubishi S6R-PTAS6R Series S6R-PTA

Technical Specifications

BrandMitsubishi
ModelS6R-PTA
SeriesS6R Series
ConfigurationL6
Cylinders6
Displacement24.51 L
Dry Weight2800 kg
Dimensions (L×W×H)1946 × 862 × 1498 mm
Fuel TypeDiesel
Ignition TypeCompression Ignition
Cooling MethodLiquid-Cooled
Emissions StandardUnregulated
Country of OriginJapan

Frequently asked questions

What is the power output of the Mitsubishi S6R-PTA?

The Mitsubishi S6R-PTA is rated at 677 kVA standby / 612 kVA prime at 50 Hz (1,500 rpm); and 778 kVA standby / 707 kVA prime at 60 Hz (1,800 rpm).

Does the S6R-PTA run at 50 Hz or 60 Hz?

The Mitsubishi S6R-PTA is available for both 50 Hz (1,500 rpm) and 60 Hz (1,800 rpm).

What fuel does the Mitsubishi S6R-PTA use?

The Mitsubishi S6R-PTA is a diesel generator-set engine.

What is the displacement and cylinder configuration of the S6R-PTA?

The Mitsubishi S6R-PTA is an inline-6 (6-cylinder) engine with a displacement of 24.51 L.

Is the Mitsubishi S6R-PTA still in production?

Yes — the Mitsubishi S6R-PTA is a current production model.

Is a datasheet available for the S6R-PTA?

Yes — an official Mitsubishi datasheet for the Mitsubishi S6R-PTA can be downloaded from this page.

Reference

Last database update
2026-07-23
Manufacturer files
1 datasheet linked

Need this engine?

Need a generator package using this engine? Haifeng Machinery can help with sizing, alternator selection, controller, enclosure, voltage, and compliance support.

Get a Quote ↗

Or browse Haifeng's diesel generator sets